A Jaga classic with a discreet, slimline design with perforated grill and flat front panel, now upgraded with Hybrid technology for optimized output.
"Experience year-round comfort with a sleek, stylish convector that cools in summer and heats in winter. Designed with a focus on style and functionality for seamless integration into any modern space."
JAGA ACO (D09)
- The fan speed is selected manually in 3 modes via the control panel.
- When the water temperature is lower than 24°C and the air is warmer than the water in the heat exchanger, the fans will start. The unit will then cool the area.
- When the water temperature is higher than 28°C and the air is colder than the water, the fans will start. The unit will then heat the area.
- The unit will automatically switch from heating to cooling and to standby mode.
JAGA BMS 0-10V CONTROL (D03)
- The fan speed is only controlled by a 0-10V (DC) signal via an external control system that is installed into the electronics of the unit. The 0-10V signal can come from a Jaga thermostat or another home automation or building management system.
- When the control voltage is 1V or higher and the water temperature is higher than 28°C or lower than 24°C, the fans will start rotating. The rotational speed will increase proportionally with the configured control voltage. At 10V control voltage, the fans will rotate at maximum rotational speed.
- When a Hybrid unit with Jaga BMS control is equipped with a thermoelectric valve motor connected to the internal electronics, the valve will open when the control voltage exceeds 1V.
JAGA TPT (D01)
- The fan speed is automatically controlled in function of the preset comfort temperature via the fingertip controls. This allows the unit to be very silent once the comfort temperature is reached.
- When a Hybrid unit with Jaga TPT control is equipped with a thermoelectric valve motor connected to the internal electronics, the unit will take over the function of room thermostat. Based on the room temperature measurement, the unit will then switch on or off the water flow through the unit itself.
- If you wish to set the room temperature via another system that enables or disables the water flow through the unit, you do not need to connect a thermoelectric valve motor to the internal controller. The TPT controller will then only control the fan rotational speed based on the set comfort temperature. Intuitively, you will then use the fingertip control to get more or less fan support when the comfort temperature is reached.
- When the water temperature in the heat exchanger is lower than 24°C, the fans will start. The unit will cool the area.
- When the water temperature is higher than 28°C, the fans will start. The unit will heat the area.
Output
Linea Plus Hybrid
Height [cm] | Length [cm] | Type | Position | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
wdt_ID | wdt_created_by | wdt_created_at | wdt_last_edited_by | wdt_last_edited_at | Height [cm] | Length [cm] | Type | Position | Light Cooling (16/18/27°C) [Watts] | Heating (35/30/20°C) [Watts] | Heating (45/40/20°C) [Watts] | Heating (50/45/20°C) [Watts] | Heating (55/45/20°C) [Watts] | Sound Pressure Level [dB(A)] | Power consumption [Watts] | Water Volume [l] | Ordercode |
1 | jagadmin | 16/04/2025 09:33 AM | jagadmin | 16/04/2025 09:33 AM | 35 | 50 | 11 | 1 | 148 | 190 | 366 | 457 | 499 | 26,0 | 3,6 | 3,0 | LINW 035 050 11 XXX DDD |
2 | jagadmin | 16/04/2025 09:33 AM | jagadmin | 16/04/2025 09:33 AM | 35 | 60 | 11 | 1 | 191 | 246 | 474 | 592 | 647 | 26,0 | 4,8 | 4,0 | LINW 035 060 11 XXX DDD |
3 | jagadmin | 16/04/2025 09:33 AM | jagadmin | 16/04/2025 09:33 AM | 35 | 70 | 11 | 1 | 234 | 301 | 580 | 724 | 791 | 26,0 | 5,5 | 5,0 | LINW 035 070 11 XXX DDD |
4 | jagadmin | 16/04/2025 09:33 AM | jagadmin | 16/04/2025 09:33 AM | 35 | 80 | 11 | 1 | 276 | 355 | 684 | 854 | 933 | 26,0 | 6,3 | 5,0 | LINW 035 080 11 XXX DDD |
5 | jagadmin | 16/04/2025 09:33 AM | jagadmin | 16/04/2025 09:33 AM | 35 | 90 | 11 | 1 | 317 | 408 | 786 | 982 | 1.072 | 26,0 | 6,7 | 6,0 | LINW 035 090 11 XXX DDD |
6 | jagadmin | 16/04/2025 09:33 AM | jagadmin | 16/04/2025 09:33 AM | 35 | 100 | 11 | 1 | 358 | 460 | 887 | 1.107 | 1.210 | 26,0 | 7,8 | 7,0 | LINW 035 100 11 XXX DDD |
7 | jagadmin | 16/04/2025 09:33 AM | jagadmin | 16/04/2025 09:33 AM | 35 | 110 | 11 | 1 | 401 | 516 | 995 | 1.242 | 1.357 | 26,0 | 8,4 | 7,0 | LINW 035 110 11 XXX DDD |
8 | jagadmin | 16/04/2025 09:33 AM | jagadmin | 16/04/2025 09:33 AM | 35 | 120 | 11 | 1 | 437 | 562 | 1.084 | 1.354 | 1.479 | 26,0 | 8,9 | 8,0 | LINW 035 120 11 XXX DDD |
9 | jagadmin | 16/04/2025 09:33 AM | jagadmin | 16/04/2025 09:33 AM | 35 | 140 | 11 | 1 | 515 | 662 | 1.277 | 1.595 | 1.743 | 26,0 | 10,1 | 9,0 | LINW 035 140 11 XXX DDD |
10 | jagadmin | 16/04/2025 09:33 AM | jagadmin | 16/04/2025 09:33 AM | 35 | 160 | 11 | 1 | 592 | 760 | 1.467 | 1.832 | 2.001 | 26,0 | 11,0 | 11,0 | LINW 035 160 11 XXX DDD |
11 | jagadmin | 16/04/2025 09:33 AM | jagadmin | 16/04/2025 09:33 AM | 35 | 180 | 11 | 1 | 675 | 867 | 1.673 | 2.090 | 2.283 | 26,0 | 12,2 | 12,0 | LINW 035 180 11 XXX DDD |
12 | jagadmin | 16/04/2025 09:33 AM | jagadmin | 16/04/2025 09:33 AM | 35 | 200 | 11 | 1 | 741 | 952 | 1.836 | 2.293 | 2.505 | 26,0 | 13,4 | 13,0 | LINW 035 200 11 XXX DDD |
13 | jagadmin | 16/04/2025 09:33 AM | jagadmin | 16/04/2025 09:33 AM | 35 | 220 | 11 | 1 | 809 | 1.040 | 2.005 | 2.505 | 2.736 | 26,0 | 13,4 | 15,0 | LINW 035 220 11 XXX DDD |
14 | jagadmin | 16/04/2025 09:33 AM | jagadmin | 16/04/2025 09:33 AM | 35 | 240 | 11 | 1 | 877 | 1.127 | 2.174 | 2.715 | 2.967 | 26,0 | 14,8 | 16,0 | LINW 035 240 11 XXX DDD |
15 | jagadmin | 16/04/2025 09:33 AM | jagadmin | 16/04/2025 09:33 AM | 35 | 260 | 11 | 1 | 950 | 1.220 | 2.353 | 2.939 | 3.211 | 26,0 | 16,2 | 17,0 | LINW 035 260 11 XXX DDD |
16 | jagadmin | 16/04/2025 09:33 AM | jagadmin | 16/04/2025 09:33 AM | 35 | 280 | 11 | 1 | 956 | 1.286 | 2.481 | 3.098 | 3.385 | 26,0 | 16,2 | 19,0 | LINW 035 280 11 XXX DDD |
17 | jagadmin | 16/04/2025 09:33 AM | jagadmin | 16/04/2025 09:33 AM | 35 | 50 | 11 | 2 | 158 | 203 | 391 | 489 | 555 | 30,0 | 4,1 | 7,0 | LINW 035 050 11 XXX DDD |
18 | jagadmin | 16/04/2025 09:33 AM | jagadmin | 16/04/2025 09:33 AM | 35 | 60 | 11 | 2 | 205 | 263 | 508 | 634 | 693 | 30,0 | 5,4 | 8,0 | LINW 035 060 11 XXX DDD |
19 | jagadmin | 16/04/2025 09:33 AM | jagadmin | 16/04/2025 09:33 AM | 35 | 70 | 11 | 2 | 251 | 322 | 622 | 777 | 849 | 30,0 | 5,9 | 9,0 | LINW 035 070 11 XXX DDD |
20 | jagadmin | 16/04/2025 09:33 AM | jagadmin | 16/04/2025 09:33 AM | 35 | 80 | 11 | 2 | 296 | 381 | 735 | 917 | 1.002 | 30,0 | 6,8 | 11,0 | LINW 035 080 11 XXX DDD |
21 | jagadmin | 16/04/2025 09:33 AM | jagadmin | 16/04/2025 09:33 AM | 35 | 90 | 11 | 2 | 341 | 438 | 846 | 1.056 | 1.154 | 30,0 | 7,4 | 12,0 | LINW 035 090 11 XXX DDD |
22 | jagadmin | 16/04/2025 09:33 AM | jagadmin | 16/04/2025 09:33 AM | 35 | 100 | 11 | 2 | 385 | 495 | 955 | 1.193 | 1.303 | 30,0 | 8,7 | 13,0 | LINW 035 100 11 XXX DDD |
23 | jagadmin | 16/04/2025 09:33 AM | jagadmin | 16/04/2025 09:33 AM | 35 | 110 | 11 | 2 | 432 | 556 | 1.072 | 1.339 | 1.462 | 30,0 | 9,3 | 15,0 | LINW 035 110 11 XXX DDD |
24 | jagadmin | 16/04/2025 09:33 AM | jagadmin | 16/04/2025 09:33 AM | 35 | 120 | 11 | 2 | 473 | 607 | 1.171 | 1.463 | 1.598 | 30,0 | 9,9 | 16,0 | LINW 035 120 11 XXX DDD |
25 | jagadmin | 16/04/2025 09:33 AM | jagadmin | 16/04/2025 09:33 AM | 35 | 140 | 11 | 2 | 558 | 717 | 1.383 | 1.728 | 1.887 | 30,0 | 11,2 | 19,0 | LINW 035 140 11 XXX DDD |
Composition of the order code
Hover over the parts below to find out what they stand for
LINW
035
050
11
XXX
DDD
-
Linea Plus Hybrid Brochure
Brochure
-
Linea Plus Hybrid Manual
Manual
-
Selection tool Low-H2O Hybrid
Selection tool
Standard delivery
- Low-H2O heat exchanger, with dirt and dust repellent coating in graphite grey (RAL 7024)
- wall brackets and mounting set
- angled air vent (standard and Height 020) or extended 1/8" air vent (twin) and 1/2" drain cock
- partially assembled casing for a connection on the bottom left or bottom right
- easy to install fan unit with operation, control and 24VDC power supply
This heater is not equipped with a condensation monitor. It has to be integrated into the installation (only for cooling).